American standard switchgear for current transformers used in relay/zero sequence protection
The current transformer used for relay protection under high current conditions must have a relay rating. This rating is represented by the letter "C" or the letter "T" followed by a number. This number represents the voltage output at the CT terminal, with a current of 20 times the normal secondary current (typical 5A secondary CT is 100A), and a ratio error of no more than 10%. The standard values are 10, 20, 50, 100, 200, and 400. C "or" T "describes the method used to determine the voltage.

The voltage of CT with the "T" symbol has been determined through testing, which is a common method for block CT. IEEE power system relay requirements state that low transformation ratio CTs applied to systems with high fault current levels may saturate under fault conditions and result in improper or inoperable overcurrent relay operation. The extreme saturation of CT can result in very narrow secondary current pulses, only a few electrical degrees wide. Although the amplitude of the pulse may be higher than the pickup setting of the relay, the time for the current to flow once is not enough to operate the relay. To ensure that the CT does not saturate, the relay rating of the CT should be twice the voltage required to drive the maximum fault current through the connected load.
For example, suppose a busbar has an expected fault current of 24kA and a CT rating of 400/5A (a ratio of 80:1). Divide 24000 A by CT ratio of 80 to determine the secondary current of 300 A under maximum fault conditions. If the secondary load is 0.33 ohms, the required voltage is 300x0.33 or 100 V. A CT with a relay rating of C200 or T200 should be selected for this application.

When a low ratio CT is required on a system with high available fault current, it may be difficult to find a CT with the necessary relay rating. Several possible methods to improve this situation are to use a higher ratio CT, use a higher precision CT, use a lower load relay, distribute the load between two sets of CTs, or use a separate instantaneous overcurrent relay connected to a single set of high ratio CTs. Instantaneous grounding fault relay (50GS) and zero sequence current transformer
It is necessary to ensure that the CT does not saturate and to operate the instantaneous ground fault relay connected to the zero sequence or core balanced CT. Based on this concern, experiments were conducted to examine the operation of typical CT relay combinations. Two CTs were used to test two different relays. The relay is GE HFC and ABB IT.
Choose electromechanical relays for testing because the higher their load, the greater the load on the CT. The CT used is manufactured by GE ITI. The first model 141-500, 50/5, C10 precision. The second one is 143-500 type, 50/5, C20 precision.


These two relays operate correctly and reliably on both CTs. We also tested the third relay, ABB ITH, This relay is unreliable in this service. It starts working at relatively low values and operates well at primary currents up to 150 A. At high currents of 600 A and above, its jitter is very severe, and there is no long-term closure of contacts to operate the circuit breaker. Based on this information and testing, it is recommended not to use the ITH relay as a 50GS relay. In summary, HFC and IT operate well under a ground fault current of up to 1800A, even when CT is severely saturated at that current level. This circuit, as well as these CTs and relays, should not be used in firmly grounded systems with high ground fault currents. For these systems, residual current relays should be used, or zero sequence CTs should have a higher ratio.
Recently Posted
-
Design suggestions for American standard 38kV 3000A armored switchgear
November 18, 2026According to the American standard IEEE C37.20.2, for continuous current (temperature rise) testing, a copper bar specification is
Read More -
Design of American standard 27kV switchgear
November 18, 202627kV is the voltage level of switchgear in North American medium voltage distribution systems, defined in IEEE standards as 27kV,
Read More -
Comparison of Applicability between UL1558 Switchgear and UL891 Distribution Panel
November 16, 2026The UL1558 SWITCHGEAR switchgear is larger and more expensive than the UL891 SWITCHBOARD distribution panel, but more reliable, wh
Read More -
Gas Calculation for Inflatable Cabinets
November 16, 2026As is well known, SF6 is a greenhouse gas, and emitting 1 ton of SF6 is equivalent to emitting 23500 tons of CO2. Therefore, the d
Read More